Description
APPLICATION:
Multicore round cables are used in Elevators, Motors, Plug in cords, Panel Board Wiring, Hand Grinders, cutter cords & Automobile wires.
DESIGN:
CONDUCTOR | Annealed electrolytic flexible conductor class 2 or Class 5 ( the copper wires are flexible) | |||||||
INSULATION | PVC | |||||||
CORE COLORS | Red, Yellow, Blue | |||||||
SHEATH | PVC Black | |||||||
TEMPERATURE RANGE | -15 0C TO 70 0C |
3 CORE ROUND CABLES AS PER IS:694 WITH ISI MARK:
Conductor
|
Insulation | Sheath | Overall Dimension |
Technical Parameter
|
||
Area
sq mm |
Nos & Dia of Wire
(No/mm) |
Thickness
(Nom.) (mm) |
Thickness
(Nom.) (mm) |
Diameter
(Approx.) ‘D’ mm |
Conductor
Resistance @20 0 C (Max) ohms/km |
Current Carrying Capacity
@ 40 0 C Amps |
0.50 | 16/0.20 | 0.60 | 0.90 | 6.50 | 39.000 | 4.00 |
0.75 | 24/0.20 | 0.60 | 1.00 | 6.90 | 26.000 | 7.00 |
1.00 | 14/0.30 | 0.80 | 1.00 | 7.30 | 19.500 | 11.00 |
1.50 | 22/0.30 | 0.60 | 0.90 | 7.90 | 12.100 | 14.00 |
2.50 | 36/0.30 | 0.70 | 1.00 | 9.60 | 7.410 | 18.00 |
4.00 | 56/0.30 | 0.80 | 1.00 | 11.10 | 4.950 | 26.00 |
6.00 | 84/0.30 | 0.80 | 1.10 | 13.20 | 3.30 | 33.000 |
STANDARD PACKING LENGTH OF CABLE:
- 100 meter coil,500 meter drum,1000 meter drum or as per customer requirements
NOTE:
- The number of wire is approximate and wire diameter is nominal; they shall be such as to satisfy the requirements of conductor resistance of IS 694 / IS 8130 / BS 6360.
- Specification given here are subject to change without notice as per our design improvement requirements.